CERTIFICATIONS
----------------------------------------------------------------------------------------------------------------------------------

ISO CERTIFICATION

UNI EN ISO 9001:2000 certification with DNV certificate
            n° CERT-01575-97-AQ-FLR-SINCERT, 08 January 2009

UNI EN ISO 14001:1996 certification with DNV certificate
            n° CERT-1064-2004-AE-FLR-SINCERT, 19 January 2009

CESI CERTIFICATION

CESI test report n A6/016757, 16 june 2006
carried out on Magrini Galileo switches type 17F500.
Tests based on the IEC 62271-100 (2001-05) standard ed. 1.0.
Tests carried out:
   Three-phase short-circuit test; T10 test cycle with 1,45 kA and 15,6 kV
   Three-phase short-circuit test; T100s test cycle with 14,1 kA and 15,6 kV
   Three-phase load test with an active load of
1250A e 6,3 kV

CESI test report n° GPS-A3/036989, 3 november 2003
carried out on Magrini switches type 7F650.
Tests based on the IEC 62271-100 (2001-05) standard ed. 1.0
Tests carried out:
    Three-phase short-circuit test; T10 test cycle with 35 kA and 7,2 kV
    Three-phase short-circuit test; T100s test cycle with 35 kA and 7,2 kV
    Three-phase load test with an active load of
        1250A and 7,2 kV

CESI test report n° A5/050/0318, 25 october 2005
carried out on Ansaldo switches type MAGII.
Tests based on the
IEC 62271-100 (2001-05) standard ed. 1.0.
Tests carried out:
    Three-phase short-circuit test; T10 test cycle with 31,5 kA and 6,3 kV
    Three-phase short-circuit test; T100s test cycle with 31,5 kA and 6,3 kV
    Three-phase load test with an active load of
    1250A and 6,3 kV


 
 

company profile
| industry solutions | products gallery | certifications | contact | location
--------------------------------------------------
TOSTI SRL - Loc. Marinella 17/a - 58033 Castel del Piano GR - Italy - Tel +39.0564.955358